Switch Amplifier KFD2-SOT3-Ex1.LB.IO

Switch Amplifier KFD2-SOT3-Ex1.LB.IO
1-channel isolated barrier
24 V DC supply (Power Rail)
Dry contact or NAMUR inputs
Usable as signal splitter (1 input and 2 outputs)
Isolated passive transistor output, non-polarized
Isolated passive fault output, non-polarized
Line fault detection (LFD)

Categories: , SKU: KFD2-SOT3-Ex1.LB.IO-1-1
  • Richard Yang
  • Tel/WhatsApp: +86 18702500702
  • Email:sales@xiqian-automation.com

Description

The KFD2-SOT3-Ex1.LB.IO is a switch amplifier made by Pepperl+Fuchs .

It acts as an electronic interface for industrial applications, specifically in process automation environments.

KFD2-SOT3-Ex1.LB.IO

KFD2-SOT3-Ex1.LB.IO

Here’s a breakdown of the product description, parameters, and application:

Product Description:

  • Isolates signals: This means it electrically separates the input signal from the output signal, preventing electrical interference between them.
  • Amplifies weak signals: It can boost the strength of a low-power input signal to a higher level suitable for further processing.
  • Functions as a signal splitter: It can take a single input signal and duplicate it to two separate outputs.

Product Parameters:

  • Supply voltage: 24 V DC
  • Inputs: Supports dry contact (electrical switch) or NAMUR (industry standard for proximity sensors) sensors.
  • Outputs: Two isolated passive transistor outputs, not polarity sensitive (can be connected either way).

Product Application:

This switch amplifier is typically used in industrial automation settings where:

  • There’s a need to isolate signals to prevent electrical noise or ground loops from affecting the system.
  • A weak signal from a sensor needs to be amplified for reliable transmission.
  • A single sensor signal needs to be distributed to two control devices.

Some common applications include:

  • Connecting sensors to Programmable Logic Controllers (PLCs) in industrial control systems.
  • Interfacing with safety devices in hazardous areas.
  • Distributing sensor signals to multiple monitoring or control points.

 

Datasheet excerpt: Technical data of  KFD2-SOT3-Ex1.LB.IO

General specifications
Signal type Digital Input
Functional safety related parameters
Safety Integrity Level (SIL) SIL 2
Systematic capability (SC) SC 3
Supply
Connection Power Rail or terminals 14+, 15-
Rated voltage 19 … 30 V DC
Ripple ≤ 10 %
Rated current 20 … 15 mA
Power dissipation ≤ 1 W including maximum power dissipation in the output
Input
Connection side field side
Connection terminals 1+, 2+, 3-
Rated values acc. to EN 60947-5-6 (NAMUR), see manual for electrical data
Open circuit voltage/short-circuit current approx. 10 V DC / approx. 8 mA
Switching point/switching hysteresis 1.2 … 2.1 mA / approx. 0.2 mA
Line fault detection breakage I ≤ 0.1 mA , short-circuit I ≥ 6.5 mA
Pulse/Pause ratio min. 100 µs / min. 100 µs
Output
Connection side control side
Connection output I: terminals 7, 8 ; output II: terminals 10, 11
Rated voltage 30 V DC
Rated current 100 mA , short-circuit protected
Response time ≤ 200 µs
Signal level 1-signal: (external voltage) – 3 V max. for 100 mA
0-signal: blocked output (off-state current ≤ 10 µA)
Output I signal ; Transistor
Output II signal or fault message ; Transistor
Collective error message Power Rail
Transfer characteristics
Switching frequency ≤ 5 kHz
Galvanic isolation
Input/Output reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Input/power supply reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Output/power supply basic insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Output/Output basic insulation according to IEC/EN 61010-1, rated insulation voltage 60 Veff
Indicators/settings
Display elements LEDs
Control elements DIP switch
Configuration via DIP switches
Labeling space for labeling at the front
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EU EN 61326-1:2013 (industrial locations)
Conformity
Electromagnetic compatibility NE 21:2012 , EN 61326-3-2:2008
Degree of protection IEC 60529:2001
Input EN 60947-5-6:2000
Ambient conditions
Ambient temperature -20 … 60 °C (-4 … 140 °F)
Mechanical specifications
Degree of protection IP20
Connection screw terminals
Mass approx. 150 g
Dimensions 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) (W x H x D) , housing type B2
Height 119 mm
Width 20 mm
Depth 115 mm
Mounting on 35 mm DIN mounting rail acc. to EN 60715:2001
Data for application in connection with hazardous areas
EU-type examination certificate EXA 16 ATEX 0016 X
Marking Ex-Hexagon II 3(1)G Ex nA [ia Ga] IIC T4 Gc
Ex-Hexagon II (1)D [Ex ia Da] IIIC
Ex-Hexagon I (M1) [Ex ia Ma] I
Input Ex ia
Voltage 10.5 V
Current 17.1 mA
Power 45 mW (linear characteristic)
Supply
Maximum safe voltage 253 V AC (Attention! Um is no rated voltage.)
Output
Maximum safe voltage 253 V AC (Attention! The rated voltage can be lower.)
Galvanic isolation
Input/Output safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Input/power supply safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Directive conformity
Directive 2014/34/EU EN IEC 60079-0:2018+AC:2020 , EN 60079-11:2012 , EN 60079-15:2010
International approvals
UL approval E106378
Control drawing 116-0424 (cULus)
IECEx approval
IECEx certificate IECEx EXA 16.0009X
IECEx marking Ex nA [ia Ga] IIC T4 Gc , [Ex ia Da] IIIC , [Ex ia Ma] I
General information
Supplementary information Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.